Easytop concealed straight seat valve
with SC‑Contur
for drinking water installation
Trade mark rights exist for this document, further information can be found at www.viega.com/legal-notices.
The information in this manual is directed at heating and sanitary professionals and trained personnel.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instruction for use.
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
This symbol warns against possible life-threatening injury.
This symbol warns against possible serious injury.
This symbol warns against possible injury.
This symbol warns against possible damage to property.
Notes give you additional helpful tips.
The use of the model for areas of use and media other than those described must be approved by the Viega Service Center.
Use is possible in the following areas, amongst others:
Drinking water installations
- with Sanfix Fosta PE‑Xc/Al/PE‑Xc pipes (dimensionally stable with external oxygen seal coat)
- with Sanfix PE‑Xc pipes (flexible without external oxygen seal coat)
The model is used for shutting off storey and floor units.
The general rules of engineering must be observed for planning, execution, operation and maintenance drinking water installations.
e. g. the following regulations apply:
DIN EN 806 part 1–5 and DIN EN 1717
Additional national regulations amongst others DIN 1988, VDI/DVGW 6023 and Drinking Water Ordinance (DWO)
The model is suitable for the following media among others:
Drinking water without limitations
in acc. with DWO
max. chloride concentration 250 mg/l
in acc. with DWO
Easytop system fittings can be used for all types of drinking water in acc. with DWO and DIN 50930‑6 and are DVGW certified. Their plastic components conform with the KTW recommendation and the requirements of the DVGW Worksheet W 270.
The Easytop system fittings comply with the testing criteria of DIN EN 1213: 1999 (Fitting group I). Sound protection Lap≤ 20 dB(A)
The model is equipped as follows:
Upper part
Site protection
Valve casing made of gunmetal
Valve seat made of stainless steel
dual-sided Sanfix P press connection with SC‑Contur
green dot for drinking water
The model is available in the following dimensions: d 16 / 20 / 25 / 32.
Viega press connections are equipped with the SC‑Contur. The SC‑Contur is a safety technology that is certified by the DVGW and ensures that the connection is guaranteed to be leaky in an unpressed state. In this way, unpressed connections are noticed immediately during a leakage test.
Viega guarantees that unpressed connections are visible during a leakage test:
with the wet leakage test in the pressure range from 1.0–6.5 bar
with dry leakage test in the pressure range from 22 mbar–3.0 bar
Only EPDM sealing elements are permitted in drinking water installations. Other sealing elements may not be used.
The model is factory-fitted with EPDM sealing elements.
Area of use |
---|
Area of use |
Operating temperature [Tmax] |
Operating pressure [Pmax] |
Comments: |
Drinking water |
---|
All sections of pipe |
70 °C |
10 bar |
see note Media |
The press connections are marked with a coloured dot. This identifies the SC‑Contur, where the test medium would escape in the case of an inadvertently unpressed connector.
The model is marked as follows:
Flow of direction indicator
Noise class I in acc. with DIN EN 1213
Dimension
DVGW writing
green dot for drinking water
Position indicator
The model is equipped with Sanfix P press connections and compatible with the Sanfix/Sanfix Fosta systems.
Observe the following operating conditions for the installation of the model:
Operating temperature [Tmax] |
---|
Operating pressure [Pmax] |
70 °C |
10 bar |
Uncovered pipes and fittings in rooms do not normally require external corrosion protection.
There are exceptions in the following cases:
Contact with aggressive building materials such as nitrite or materials containing ammonium
Contact with aggressive chemicals
in aggressive surroundings
If external corrosion protection is required, the following regulations should be followed:
DIN EN 806‑2
DIN 1988‑200
DKI information publication i. 160
Easytop fittings made of gunmetal are suitable for all types of drinking water.
The chloride concentration in the medium must not exceed 250 mg/l.
This chloride is not a disinfectant, but in fact pertains to the content in sea and table salt (sodium chloride).
The following optional accessories are available:
Insulating shell
Equipment sets
Public building model
Mounting sets
Do not remove the model from the packaging until immediately before use.
System components may, in some cases, become damaged through transportation and storage.
Check all parts.
Replace damaged components.
Do not repair damaged components.
Contaminated components may not be installed.
Observe the following when mounting the model:
minimum / maximum installation depth
Use suitable tool
Choose the place of installation so that the fitting is easily accessible, simple to operate and the insulating shell can be well mounted.
Information can be found in the Sanfix / Sanfix Fosta system instructions for use.
Information can be found in the Sanfix / Sanfix Fosta system instructions for use.
The following tools are required for production of a press connection:
Hand or electric saws or angle grinders are not permitted.
Press tool with constant pressing force
suitable Sanfix press jaws for PE‑Xc systems (model 2299.7 or 2484.7)
Pipe shear (model 5341) for dimensions 16–25 mm
Pipe cutter (model 2191) for dimensions 32–63 mm
Bending tool (model 5331 or 5331.2)
Calibrated to the pipe size:
16 / 20 mm (model 2139.0)
25 / 32 / 40 mm (model 2139.3)
Recommended Viega press tools:
Pressgun 5
Pressgun Picco
Pressgun 4E / 4B
Picco
Type PT3-AH
Type PT3-H / EH
Type 2 (PT2)
Leaky press connections due to damaged material
Press connections can become leaky due to damaged pipes.
See Required tools for information about tools.
Cut the protective pipe to length with the protective pipe cutter (model 5341).
Cut pipe to length properly using a pipe shear.
Replace worn blades (model 5341.6).
clean, even cutting surface (graphic bottom right)
Cut the pipe to length properly using a pipe cutter (model 2191).
Information regarding the intervals can be found in the Sanfix / Sanfix Fosta system instructions for use.
Push the pipe into the press connector until the pipe end is visible in the inspection window.
Check insertion depth in the inspection window.
Open press jaw and place at a right-angle onto the connector. Start pressing.
Connection is pressed.
A functionality test must be carried out after mounting.
Installation is possible in masonry (wet construction) and in dry constructions (pre-wall / duct installations).
Attach the fitting from behind with the fixing set onto a Viega fitting holder with slot nuts.
Seal wall lead-in on the front side of the wall with the self-adhesive sealing flange.
Attach the protective sleeve in front of and behind the cladding (e. g. sheetrock or Fermacell panels) with lock nuts.
Seal wall lead-in on the front side of the wall with the self-adhesive sealing flange.
Open or close the valve clockwise or anti-clockwise respectively.
During the preliminary building work phases:
Actuate the valve via the protective cap.
The installer must perform a leakage test (load and leakage test) before commissioning.
This test is carried out on a unit that is finished but not yet covered.
The general rules of engineering must be observed.
e.g. the following regulations apply:
DIN EN 806–4
Data sheet "Leakage tests of drinking water installations with compressed air, inert gas or water"
The result must be documented.
Inform your customer or the operator of the drinking water installation that the system has to be maintained on a regular basis.
DIN EN 806‑5 must be observed for the operation and maintenance of drinking water installations.
We recommend actuating the fitting regularly and checking its function.
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.